Menu
Our Location on Google mapsFollow Us on Linkedin
My Bag

Your bag is currently empty.

Fire Pump Controllers

Fire Pump Controllers - Jockey/Jacking Pump

FPC-70000 Range

MATelec Australia’s Jockey/Jacking Pump Controller is designed to provide control and status indication for a jockey/jacking pump, compliant with the current Australian Standards (AS 2941-2013: Section 5). Housed in a red powder coated metal enclosure, the controller features pump overload protection, a digital input for automatic pump control and an LCD screen/keypad interface with pump status indication, logged data and auto/off/manual control.

  • Enclosure:
    • IP54 rated, powder coated mild steel enclosure with removable gland plate
  • Protection:
    • Mains power isolator switch (pad-lockable in on position)
    • Circuit breaker protected low voltage control and input circuitry
    • Contactor and thermal overload protection of pump
    • Din rail mounted terminal connections
  • Control & interface:
    • HMI with backlit LCD screen and keypad:
      • System and pump status overview screen
      • Auto, off/reset and manual control buttons
      • Logged data for start and fault counters, pump run hours
    • Jacking pump controller PCB control module
      • Config button for adjusting settings, resetting logged data
  • Inputs:
    • Single phase (230Vac) or three phase (400Vac) power supply
    • Digital 12Vdc input for pressure switch/pump start signal
  • Outputs:
    • Pump supply output
    • BMS volt free output for pump fault

Function Features

  • Provides status indication and control for a jockey/jacking pump, compliant with the current Australian Standards (AS 2941-2013: Section 5)
  • Automatic control via digital input
  • Momentary manual pump run while manual button is held down, before returning to auto
  • Momentary pump off while off/reset button is held down, before returning to auto
  • Optional pump run timer keeps pump running for adjustable period of time after the pump start input opens

Fault Protection

  • Pump overload protection shuts down pump on overload

Jockey/Jacking Pump Range

Code Phase / Voltage Overload Rating Options Enclosure Size
FPC-70011 1 Phase / 230Vac -AA to -E 300x300x150mm
FPC-70013 3 Phase / 400Vac -AA to -E 300x300x150mm

Overload Rating Guide

Code Suffix Amp Rating
-AA 1.6 - 2.5 Amp
-A 2.5 - 4 Amp
-B 4 - 6 Amp
-BB 5.5 - 8 Amp
-C 7 - 10 Amp
-D 9 - 13 Amp
-E 12 - 18 Amp

Additional overload ratings available on request

 

Available