Single Phase Dual Pump with BMS Hot Water Circulation Controller
- Smart chirp mode alarms - Alarms automatically silence after 5 minutes if not muted, then chirp every 5 minutes
- Manual control - Manual pump mode with optional 5 minute timeout to revert back to auto mode
- Duty sharing and alternation - Duty pump alternates after 6 hours of accumulated running in circulation mode
- Controlled by - Thermostat, duty pump will run while this is closed due to water cooling down
- Adjustable operation time - Timeclock allows user to confgure the time of day/week that the system will operate during.
Enclosure
- IP56 rated, powder coated mild steel enclosure with inner door and removable gland plate
- Pad-lockable mains power isolator switch
- Circuit breaker protected low voltage control and input circuitry
- Individual pump isolation
- Contactor and thermal overload protection of pump motors
- Din rail mounted terminal connections
- Single or dual pump keypad interface:
- Indicator lights for power on, high & low level alarm, pump run, pump fault/overload and prime loss
- Push buttons for alarm mute/reset, pump auto/off/manual control
- PCB control module with dipswitches for adjusting configuration
- Visual (strobe) and mutable audible (buzzer) alarms
- Adjustable 7 day 24 hour digital Time Clock for configuring operation times when hot water will be required
Fault protection
- Pump overload protection - Shuts down pump/s on overload, with automatic duty alternation.
- Single phase (230Vac) or three phase (400Vac) power supply
- 1x digital 12Vdc input for thermostat
- 2x pump supply outputs
- BMS volt free outputs for power on, individual pump run and fault.
Overload Selection
Code Suffix | Amp Rating |
-AA | 1.6 - 2.5 Amp |
-A | 2.5 - 4 Amp |
-B | 4 - 6 Amp |
-BB | 5.5 - 8 Amp |
-C | 7 - 10 Amp |
-D | 9 - 13 Amp |
-E | 12 - 18 Amp |
Hot Water Circulation Controllers - Dual Pump with BMS - Single Phase
Code | No of Pumps | Phase / Voltage | Enclosure Size |
---|---|---|---|
FPC-30205 | Dual | 1 Phase / 230Vac | 400x400x200mm |
Additional overload ratings available on request.
Note: Enclosure sizes may increase for higher overload ratings.