Standard Pump Controllers - With Inner Door
Standard Range
- Enclosure:
- IP56 rated, powder coated mild steel enclosure with inner door and removable gland plate
- Protection:
- Pad-lockable mains power isolator switch
- Circuit breaker protected low voltage control and input circuitry
- Individual pump isolation
- Contactor and thermal overload protection of pump motors
- Din rail mounted terminal connections
- Control & interface:
- Single or dual pump keypad interface:
- Indicator lights for power on, level alarm, pump run and fault
- Push buttons for alarm mute/reset, pump auto/off/manual control
- PCB control module with dipswitches for adjusting configuration
- Visual (strobe) and mutable audible (buzzer) alarms
- Soft starter per pump with adjustable soft start and stop (Soft Start versions)
- Single or dual pump keypad interface:
- Inputs:
- Single phase (230Vac) or three phase (400Vac) power supply
- 4x digital 12Vdc inputs for float or pressure switches, optional low flow switch
- Standard terminal setup: Low level, pump stop, pump start and high level float switches
- Outputs:
- 1 or 2x pump supply outputs
- BMS volt free output for common fault
- Coded data output for connection to Remote Status Indicators, BMS Module or SMS Alarm/Status Communicator
Function Features
- High level alarm delay
- Smart chirp mode alarms
- Manual pump control
- Duty sharing and alternation
- Pump staging and destaging
- Staggered pump start
- Level control mode
- Maintain minimum level
- Pressure control mode
Fault Protection
- Pump overload protection
- Pump anti-seize protection
- High level alarm
- Low level alarm
- Low flow/prime loss protection
- Low pressure alarm
Common Applications
- Submersible sewage
- Submersible stormwater
- Pressure boosting
Standard Pump Controllers - With Inner Door
Code | No of Pumps | Phase / Voltage | Overload Ratings | Soft Starter Ratings |
FPC-15007 | 1 | 3 Phase / 400Vac | -AA to -E | -S4.0 to -S90 |
FPC-30020 | 2 | 1 Phase / 230Vac | -AA to -E | N/A |
FPC-30040 | 2 | 3 Phase / 400Vac | -AA to -E | -S4.0 to -S90 |
See the Standard - Electronic Overload Range for single phase, single pump controllers (FPC-15005)
Overload Rating Guide
Code Suffix | Amp Rating |
-AA | 1.6 - 2.5 Amp |
-A | 2.5 - 4 Amp |
-B | 4 - 6 Amp |
-BB | 5.5 - 8 Amp |
-C | 7 - 10 Amp |
-D | 9 - 13 Amp |
-E | 12 - 18 Amp |
Additional overload ratings available on request
For FLCs greater than 18 Amps, soft starters are recommended
Soft Starter Guide
Code Suffix | kW Rating |
-S4.0 | 4.0 kW |
-S5.5 | 5.5 kW |
-S7.5 | 7.5 kW |
-S11 | 11 kW |
-S15 | 15 kW |
-S22 | 22 kW |
-S30 | 30 kW |
-S37 | 37 kW |
-S45 | 45 kW |
-S55 | 55 kW |
-S75 | 75 kW |
-S90 | 90 kW |
Additional kW ratings up to 160kW available on request
Optional Modifications
- /SMS - With ME-Link module for SMS alarm/status messaging
- /BBHLS - With battery backup high level alarm
- /CON - With conductivity relays and inputs for common, stop, start and high level probes
- /GEN - With generator inlet socket and manual changeover switch
- /ATS - With automatic generator changeover switch
- /INT - With intrinsically safe input barrier relay and inputs for working and high level floats
- Pump thermistor inputs
- Mine spec enclosure
- 316 stainless steel enclosure
- Pump max run time protection