Menu
Our Location on Google mapsFollow Us on Linkedin
My Bag

Your bag is currently empty.

RainMains Controller   Dual Pump

Rain/Mains Pump Controller - Dual Pump - 1 Phase

FPC-32020
  • Enclosure:
    • IP56 weatherproof rating
    • Powder coated mild steel
    • Inner door and removable gland plate
  • Protection:
    • Padlockable mains power isolator switch
    • Circuit breaker protected low voltage control and input circuitry
    • Individual pump isolation
    • Contactor and thermal overload protection of pumps
    • Electronic short and overload protection of strobe/buzzer
  • Alarms:
    • Visual (strobe) and audible (buzzer) alarms
  • Control & interface:
    • Electronic keypad
    • Indicator lights for power on, level alarm, pump run/fault, rain/mains water and system fault
    • Audible and visual alarm mute/reset/test button
    • System test button for checking pump and valve function
    • Auto/off/manual operation of pumps
    • Dipswitches for input and operation configuration
  • Input options:
    • 4x digital 12Vdc inputs for float/pressure/flow switches
    • Standard terminal setup: Low level float switch and lead/lag/low pressure switches
  • Outputs:
    • 2x pump supply outputs
    • 1x 12Vdc output for solenoid valve
  • ​Included with panel:
    • 25mm female/female 12Vdc pulse latching solenoid valve

Function Features

  • Operation:
    • Maximum run timer and auto alternation of pump duty
    • Anti seize timer runs pumps periodically during low use
    • Optional time out on manual pump mode
    • Staggered pump start
    • Smart auto silencing and chirp mode alarm
    • If rain water becomes available, the controller pulse closes the mains water valve and the pump will provide rain water
    • In the event of rain water depletion, pump fault or power failure, the controller shuts off the pump and pulses the valve open for mains water use
  • Fault protection:
    • Pump overload fault shut-down
    • Low level pump shut-down
    • Low flow/prime loss shut-down
    • Optional maximum pump run time shut-down

Optional Modifications

  • 316 stainless steel enclosure
  • Generator input socket and automatic changeover
  • 4G SMS alarm sender
  • Conductivity relays and probe inputs
  • Other valve sizes available

FPC-32020 Range - Single Phase (230Vac)

Code Overload Rating Enclosure Size
FPC-32020-AA 1.6 - 2.5 Amp 400x400x200mm
FPC-32020-A 2.5 - 4 Amp 400x400x200mm
FPC-32020-B 4 - 6 Amp 400x400x200mm
FPC-32020-BB 5.5 - 8 Amp 400x400x200mm
FPC-32020-C 7 - 10 Amp 400x400x200mm
FPC-32020-D 9 - 13 Amp 400x400x200mm

 Alternative Overload Ratings available on request

Available